Cooling Capacity kW 3.50 4.20 5.30 6.20 7.00 8.2 9.4 13.2
Heating Capacity kW 4.00 5.40 6.20 7.30 7.90 9.1 10.2 13.8
Compressor Type BER
12EU
BER
16EU
BER
18EU
BER
21EU
BER
24EU
BER
30EU
BER
36EU
BER
48EU
Refrigerant R410A
Power Supply V/Ph/Hz 230/1/50+E
Power input
(cooling / heating)
kW 1.1/1.2 1.3/1.6 1.6/1.7 1.9/2.1 2.2/2.3 2.4/2.5 2.7/2.8 3.6/3.6
EER / COP w/w 3.2/3.4 3.2/3.4 3.4/3.6 3.2/3.4 3.2/3.4 3.4/3.6 3.4/3.6 3.4/3.6
Fuse rating A 16 16 20 20 20 25 25 25
Indoor airflow (high speed) m²/h 660 730 850 1020 1160 1380 1520 1860
Sound pressure
at 1m
Indoor dB(A) 29/32/36 32/34/40 35/37/41 36/38/42 37/40/43 38/41/43 38/41/43 38/42/44
Outdoor dB(A) 50 51 53 54 54 56 56 56
Dimensions Ind / Outd H (mm) 280/540 280/540 286/695 286/695 330/695 330/695 330/695 330/695
W (mm) 817/780 815/780 906/845 906/845 1080/845 1080/845 1080/845 1080/845
D (mm) 192/250 195/250 235/335 235/335 222/335 222/335 222/355 222/355
Net Weight Indoor unit kg 10.50 11.00 14 14 17 17 17 17
Outdoor kg 36 38 57 58 59 60 63 68
Piping Type of connection QF
Dia. Gas 1/2" 1/2" 5/8" 5/8" 5/8" 5/8" 5/8" 5/8"
Liquid 1/4" 1/4" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8"
Refrigerant charge
(c/o - h/p)
g 830-1150
1080
830-1150
1480
1380-1380
1660
1380-1380
1720
1850-1900
1880
1850-1900
2020
1850-1900
2420
1900-1950
3150
Max pipe run m 15 17 18 20 20 30 30 30
Operating limits - cooling min / max +10°C / +43°C
Operating limits - heating min / max -7°C / +28°C
Normal cooling capacity based on - Indoor Air Temp. 27°C DB / 19°C - Outdoor Air Temp. 35°C DB
Normal heating capacity based on - Indoor Air Temp. 21°C DB - Outdoor Air Temp. 7°C DB/6°C WB
Piping length: 7.5m with initial charge